Index Report

OSHA Fire Safety Citations, FY2021 to FY2025: OSHA Fire Extinguisher Inspection Requirements and Exit Rules Ranked

We coded 23,414 fire protection violations from the Department of Labor's OSHA enforcement files to rank the subparagraphs inspectors cite, what the penalties come to, and where the citations land.
Primary data
U.S. Department of Labor OSHA Violation and Inspection bulk files (data.dol.gov), coded by Fire Life and Safety
Data period
Inspections opened FY2021 to FY2025 (October 1, 2020 to September 30, 2025)
Latest release used
2026-10-27
Next release
DOL refreshes the bulk files daily; this index is rebuilt after each fiscal year closes
Geography
United States: Federal OSHA and OSHA-approved State Plans
Sources
17 (16 Tier 1)
Short answer

In 330,773 OSHA and State Plan inspections opened FY2021 to FY2025, the most cited fire rules were extinguisher access (1910.157(c)(1), 3,192 violations), blocked exit routes (2,469) and the osha fire extinguisher inspection requirements for monthly checks (2,378) and annual maintenance (1,849). Fire violations drew $61.3 million in initial penalties, $42.1 million after reductions.

How the index is built

Fire citation index

FormulaRank subparagraphs (first two paragraph levels) by count of non-deleted violations, inspections opened FY2021 to FY2025

Inputs: fact rows 1 to 6 and 43 to 62 (fact sheet rows)

Result: 1910.157(c)(1) ranks 1st with 3,192; 1910.37(a)(3) 2nd with 2,469; 1910.157(e)(2) 3rd with 2,378

Access and upkeep rules outrank equipment design rules. The index tells employers which paragraphs inspectors write up most, not which hazards cause the most harm.

Limitations: Deeper paragraph levels are pooled into their parent; OSHA paragraph coding by compliance officers varies.

Penalty reduction, initial to current

Formula1 minus (sum of current penalties / sum of initial penalties), x 100

Inputs: fact rows 7 to 42 (fact sheet rows)

Result: 31.3% across all coded fire standards; 34.0% for extinguishers; $19,187,641 removed

About a third of proposed fire penalty dollars come off through informal settlements, contests and adjustments.

Limitations: Current penalties for FY2025 cases can still change; nominal dollars.

Extinguisher citations per 1,000 inspections

Formula1910.157 violations / inspections opened in the fiscal year x 1,000, by jurisdiction

Inputs: fact rows 63 to 82 (fact sheet rows)

Result: Federal 16.22 (FY2021), 20.5 (FY2024), 15.52 (FY2025); State Plans excluding WA, CA, OR, MI 57.65, 83.72, 73.82

Extinguisher citations track the number and type of inspections more than any change in the rule, which has not changed in the period.

Limitations: Inspection mix differs by jurisdiction: construction is 51.5% of federal and 36.5% of State Plan inspections.

State Plan to federal ratio

FormulaState Plan rate (excluding WA, CA, OR, MI) / Federal rate

Inputs: tables/pooled_rates.csv (fact sheet rows)

Result: 4.08 for all employers (73.48 / 18.0); 2.8 for private employers (44.16 / 15.75)

State Plans write extinguisher items far more often per inspection, partly because they inspect public workplaces, which run at 180.3 per 1,000.

Limitations: Classification of State Plan offices is derived from the reporting office code.

Leading sector per standard group

FormulaNAICS 2022 sector with the most violations in each group

Inputs: tables/naics_by_group.csv (fact sheet rows)

Result: Manufacturing leads extinguishers (22.9%), exit routes (23.9%) and flammable liquids (44.4%); Construction leads 1926.150 to 1926.152 (95.9%); Public Administration leads other Subpart L (69.9%)

Fire citations follow where inspectors go and where fixed fire equipment is expected.

Limitations: NAICS is the inspected establishment's code at inspection.

Rank among all federally cited sections

FormulaRank of section by violations among all sections cited in federal inspections opened FY2021 to FY2025

Inputs: scripts/01_extract.py output all_violations_by_section.csv (fact sheet rows)

Result: 1910.37 ranks 21st and 1910.157 ranks 23rd

Fire rules sit just outside OSHA's annual Top 10 but are cited thousands of times.

Limitations: Five pooled years versus OSHA's single-year list.

Federal versus State Plan median penalty, 1910.157

FormulaFederal median initial penalty / State Plan median initial penalty (items with a penalty)

Inputs: tables/federal_vs_state.csv (fact sheet rows)

Result: $4,610 / $850 = 5.4

State Plans cite extinguishers more often but at much lower amounts per item.

Limitations: State Plans set their own penalty schedules.

Download the calculations (CSV)

23,414fire protection violations in inspections opened FY2021 to FY2025[1][2]
3,192violations of 1910.157(c)(1), the single most cited fire subparagraph[1]
31.3%drop from $61.3 million initial to $42.1 million current fire penalties[1]
4.08xState Plan extinguisher citation rate versus Federal OSHA (73.48 vs 18.0 per 1,000 inspections)[1][2]

The fire citation index: 20 subparagraphs ranked by violations

Four subparagraphs account for 42.2% of the 23,414 fire violations in our five-year window. Two of the top four are extinguisher upkeep rules, not equipment failures.

We read every non-deleted violation in the Department of Labor's OSHA violation file (DOL bulk file, 2026-10-27), kept items citing 29 CFR 1910.36 to 1910.39, 1910.106, 1910.155 to 1910.165 and 1926.150 to 1926.152, and joined them to the inspection file to assign a fiscal year, jurisdiction and industry. The result covers 23,414 violations in 14,586 inspections opened from FY2021 to FY2025.

1910.157(c)(1) leads with 3,192 violations. 1910.37(a)(3), exit routes free and unobstructed, follows with 2,469. The monthly visual inspection rule 1910.157(e)(2) ranks third with 2,378 and the annual maintenance rule 1910.157(e)(3) ranks fourth with 1,849. Exit marking, 1910.37(b)(2), is fifth with 1,699.

The 15 most cited OSHA fire protection subparagraphs

Violations in inspections opened FY2021 to FY2025, Federal OSHA and State Plans

The 15 most cited OSHA fire protection subparagraphsHorizontal bar chart ranking fire protection subparagraphs. 1910.157(c)(1) leads with 3,192 violations, followed by 1910.37(a)(3) with 2,469, the monthly inspection rule 1910.157(e)(2) with 2,378 and the annual maintenance rule 1910.157(e)(3) with 1,849.violations1910.157(c)(1)3,1921910.37(a)(3)2,4691910.157(e)(2)2,3781910.157(e)(3)1,8491910.37(b)(2)1,6991910.36(d)(1)7721910.157(g)(1)6861926.150(c)(1)6811910.36(g)(2)5901910.37(b)(5)5781910.37(b)(6)5741910.37(a)(4)5471910.38(b)5451910.37(b)(4)4101910.106(e)(6)392

Source: FLS analysis of U.S. Department of Labor OSHA Violation and Inspection bulk files (file date 2026-10-27)

Fire citation index: the 20 most cited fire protection subparagraphs Download CSV
RankSubparagraphWhat it requires (summary)Violations FY2021 to FY2025Serious %FederalState PlanMedian initial penaltyMedian current penalty
11910.157(c)(1)Provide extinguishers; mount, locate and identify them so they are readily accessible3,19239.61,0272,165$2,318$1,480
21910.37(a)(3)Exit routes free and unobstructed2,46961.21,3671,102$5,296$3,574
31910.157(e)(2)Monthly visual inspection of portable extinguishers2,37830.05961,782$700$586
41910.157(e)(3)Annual maintenance check, with the date recorded1,84938.35101,339$2,500$1,607
51910.37(b)(2)Each exit clearly visible and marked with an Exit sign1,69946.25491,150$2,125$1,200
61910.36(d)(1)Exit route doors open from the inside without keys, tools or special knowledge77273.2350422$4,250$3,000
71910.157(g)(1)Education program on extinguisher use where extinguishers are provided68652.6232454$2,818$1,861
81926.150(c)(1)Construction sites: fire extinguishers and small hose lines68137.9184497$750$585
91910.36(g)(2)Exit access at least 28 inches wide59052.2265325$4,755$3,134
101910.37(b)(5)Doors that could be mistaken for exits marked Not an Exit57848.3209369$2,800$2,207
111910.37(b)(6)Exit signs illuminated and distinctive in color57446.5239335$2,943$2,491
121910.37(a)(4)Sprinklers, alarms, fire doors and exit lighting kept in working order54765.3147400$4,900$4,500
131910.38(b)Emergency action plan in writing (oral plan allowed at 10 or fewer employees)54548.6149396$2,805$1,786
141910.37(b)(4)Directional signs where the way to the exit is not apparent41053.2236174$5,643$3,936
151910.106(e)(6)Industrial plants: control of ignition sources near flammable vapors39288.8200192$4,931$3,000
161910.157(c)(4)Extinguishers fully charged, operable and kept in their designated places38240.8154228$3,536$2,390
171910.157(g)(2)Extinguisher education at initial employment and at least annually35650.396260$2,486$1,356
181910.106(e)(2)Industrial plants: incidental storage and use of flammable liquids35483.3136218$3,978$2,766
191910.37(b)(1)Exit routes adequately lighted27578.268207$2,740$2,194
201910.106(d)(2)Approved containers and portable tanks for flammable liquids24979.955194$1,700$1,148

Violations are non-deleted cited items in inspections opened FY2021 to FY2025. Medians cover items with a penalty above $0. Requirement summaries are paraphrased from eCFR text as of 2026-10-23.

Source: [1][2][5][6] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); eCFR, Office of the Federal Register; eCFR, Office of the Federal Register

The index counts cited items, not inspections. An inspection that cites the same subparagraph twice adds two items, which is why 1910.157(c)(1) shows 3,192 violations in 3,182 inspections.

Violation (cited item): One row in the OSHA violation file: a standard cited on a citation, with its own type (serious, other-than-serious, repeat, willful), initial penalty and current penalty.

OSHA fire extinguisher inspection requirements: what 1910.157 citations are for

Under the osha fire extinguisher inspection requirements, employers must visually inspect extinguishers monthly and complete an annual maintenance check with a recorded date. Those two rules produced 4,227 violations in five years.

The federal rule is short. 29 CFR 1910.157(e)(2) says portable extinguishers, or hose used in their place, shall be visually inspected monthly. 1910.157(e)(3) requires an annual maintenance check and requires the employer to record the annual maintenance date and keep that record for one year after the last entry or the life of the shell, whichever is less (eCFR, 29 CFR 1910.157, current as of 2026-10-23). The monthly rule text does not list checklist items or require a written monthly log.

  • 1910.157(c)(1): provide, mount, locate and identify extinguishers so they are readily accessible: 3,192 violations, 39.6% serious.
  • 1910.157(e)(2): monthly visual inspection: 2,378 violations, 30.0% serious, median initial penalty $700.
  • 1910.157(e)(3): annual maintenance check and record: 1,849 violations, 38.3% serious, median initial penalty $2,500.
  • 1910.157(g)(1): education program where extinguishers are provided for employee use: 686 violations, 52.6% serious.
  • 1910.157(c)(4): fully charged, operable and in the designated place: 382 violations.
  • 1910.157(g)(2): education at initial employment and at least annually: 356 violations.
Fire extinguisher pressure gauge and blank inspection tag on a block wall
Illustrative photograph. Generated image, not a specific project.

Monthly inspection and annual maintenance items together total 4,227 violations, 45.7% of the 9,258 extinguisher violations in the window. For field procedures behind these rules, see our fire extinguisher inspection guide.

Penalty dollars: what OSHA proposes and what remains on the record

Fire violations carried $61.3 million in initial penalties and $42.1 million in current penalties. Most extinguisher items carried no penalty at all.

Across all coded fire standards, initial penalties totaled $61,336,140 and current penalties $42,148,499, a reduction of 31.3% or $19,187,641. Extinguisher items fell 34.0%, from $9,378,971 to $6,188,813. Exit route items fell 31.1%, from $41,795,228 to $28,808,863.

Fire standard groups: volume, severity and penalty dollars Download CSV
Standard groupViolationsInspections citedSerious %Repeat or willful %Initial penalties (total)Current penalties (total)Reduction initial to current %Items with $0 initial penalty %
Exit routes and emergency plans (1910.36 to 1910.39)9,7127,09056.43.2$41,795,228$28,808,86331.152.2
Portable fire extinguishers (1910.157)9,2586,87938.71.9$9,378,971$6,188,81334.071.7
Flammable liquids (1910.106)2,1481,56780.50.9$6,822,967$4,653,39831.842.8
Construction fire protection (1926.150 to 1926.152)1,2001,08243.81.8$1,979,060$1,477,35725.442.9
Other fire protection, Subpart L (1910.155 to 1910.165)1,09672076.62.6$1,359,913$1,020,06825.081.7
All coded fire standards23,41414,58652.02.4$61,336,140$42,148,49931.359.9

Nominal dollars. Current penalty = amount after settlement, contest or adjustment as recorded on 2026-10-27.

Source: [1] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal)

Median penalty per cited item: initial versus current

Items with a penalty above $0, inspections opened FY2021 to FY2025

Median penalty per cited item: initial versus currentSlope chart. The median extinguisher penalty fell from $2,024.50 initial to $1,170 current; exit route items fell from $4,465 to $2,903.40; flammable liquids from $4,103 to $2,683.Median initialMedian currentExit routes and plans 4,4652,903 Exit routes and plansExtinguishers 1910.157 2,0241,170 Extinguishers 1910.157Flammable liquids 1910.1 4,1032,683 Flammable liquids 1910.1Construction 1926.150 to 2,3411,492 Construction 1926.150 toOther Subpart L 4,0182,800 Other Subpart L

Source: FLS analysis of DOL OSHA Violation bulk file (2026-10-27)

Medians are computed only over items with a penalty above $0, because OSHA often records a grouped penalty on one line and $0 on related lines. 71.7% of extinguisher items had a $0 initial penalty. Among federal serious extinguisher items with a penalty, the middle half of initial penalties ran from $2,765 to $6,453, with a median of $4,839; 38.4% of the 1,041 federal serious extinguisher items carried $0.

OSHA penalty limits in force (federal) Download CSV
Violation typeRuleMinimumMaximumUnit
Serious29 CFR 1903.15(d)(3)$0$16,550per violation
Other-than-serious29 CFR 1903.15(d)(4)$0$16,550per violation
Repeated29 CFR 1903.15(d)(2)$0$165,514per violation
Willful29 CFR 1903.15(d)(1)$11,823$165,514per violation
Failure to abate29 CFR 1903.15(d)(5)$0$16,550per day

Amounts for penalties proposed after 2025-01-15. No 2026 adjustment was made. State Plans set their own amounts.

Source: [8][10][11] eCFR, Office of the Federal Register; U.S. Department of Labor, Federal Register; U.S. Department of Labor, Federal Register

The ceilings in 29 CFR 1903.15(d) apply to penalties proposed after January 15, 2025: $16,550 per serious or other-than-serious violation and $165,514 per willful or repeated violation, with a willful minimum of $11,823 (eCFR, 29 CFR 1903.15). The Department of Labor made no 2026 adjustment (91 FR 31358, 2026-05-27).

Serious or other-than-serious: how fire hazards are classified

Flammable liquid and fire brigade items are mostly serious. Extinguisher items are mostly other-than-serious.

Serious versus other-than-serious, by fire standard group

Share of violations, inspections opened FY2021 to FY2025

Serious versus other-than-serious, by fire standard groupGrouped bar chart. Flammable liquids violations were 80.5% serious, exit routes 56.4%, construction fire protection 43.8% and portable extinguishers 38.7%, where 59.4% were other-than-serious.020.040.060.080.0100% of violations56.440.4Exit routes andplans38.759.4Extinguishers1910.15780.518.5Flammable liquids1910.10643.854.3Construction1926.150 to .15276.620.8Other Subpart LSeriousOther-than-serious

Source: FLS analysis of DOL OSHA Violation bulk file (2026-10-27)

80.5% of flammable liquid (1910.106) violations were serious, against 56.4% for exit routes and emergency plans and 38.7% for extinguishers. Repeat or willful items were rare: 2.4% of all coded fire violations.

Serious violation: Under section 17(k) of the Occupational Safety and Health Act, a violation where there is a substantial probability that death or serious physical harm could result from a condition or practice the employer knew or could have known of with reasonable diligence (OSH Act section 17, U.S. Code via Cornell LII).

Fire brigade rules in 1910.156 behave differently. 1910.156(d), annual inspection of fire fighting equipment, drew 242 violations, all in State Plan inspections, and 97.9% were serious. OSHA's State Plans page notes that state and local government workers are not covered by Federal OSHA, so public fire departments appear only where a State Plan inspects them (OSHA State Plans).

Federal OSHA versus State Plans: four times the extinguisher citation rate

State Plans that cite federal standard numbers record extinguisher violations at 4.08 times the federal rate. Public sector inspections and inspection mix explain part of the gap, not all of it.

OSHA lists 22 State Plans covering private and public workers and 7 covering state and local government workers only (OSHA State Plans, archived 2026-10-17). We marked an inspection as State Plan when the reporting office code has 5 as its third digit. That code matched OSHA's State Plan list in our checks: in states without a State Plan, nearly all inspections carried another code.

Federal OSHA versus State Plans: citation rates per 1,000 inspections Download CSV
Jurisdiction and employer typeInspections FY2021 to FY20251910.157 violations1910.157 per 1,000 inspectionsFire violationsFire violations per 1,000 inspections
Federal155,3732,79718.08,39054.0
State plan175,4006,46136.8415,02485.66
State plan excl. WA, CA, OR, MI86,7916,37773.4814,757170.03
Federal, private employers151,7272,38915.757,55449.79
State plan excl. WA, CA, OR, MI, private employers68,0993,00744.167,449109.38
State plan excl. WA, CA, OR, MI, state and local government18,6913,370180.37,308390.99
All330,7739,25827.9923,41470.79

State Plan offices identified by reporting_id digit 3 = 5. WA, CA, OR and MI cite mostly state code numbers.

Source: [1][2][13] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); OSHA (osha.gov page, archived copy by Internet Archive on 2026-10-17)

Federal OSHA cited 1910.157 at 18.0 violations per 1,000 inspections. State Plans excluding Washington, California, Oregon and Michigan cited it at 73.48 per 1,000, a ratio of 4.08. Limiting both sides to private employers narrows the ratio to 2.8 (44.16 versus 15.75). State Plan inspections of state and local government workplaces ran at 180.3 per 1,000. Construction makes up 51.5% of federal inspections and 36.5% of State Plan inspections, and construction draws few extinguisher citations.

Extinguisher citations per 1,000 inspections by fiscal year

29 CFR 1910.157 violations per 1,000 inspections opened, by jurisdiction

Extinguisher citations per 1,000 inspections by fiscal yearLine chart. Federal OSHA cited 1910.157 at 16.22 per 1,000 inspections in FY2021, 20.5 in FY2024 and 15.52 in FY2025. State Plans that cite 29 CFR numbers ran at 57.65 in FY2021, 83.72 in FY2024 and 73.82 in FY2025.020.040.060.080.0100per 1,000 inspectionsFY2021FY2022FY2023FY2024FY2025Federal OSHAState Plans excl. WA, CA, OR, MIAll State Plans

Source: FLS analysis of DOL OSHA Violation and Inspection bulk files (2026-10-27)

Severity and median penalties, Federal OSHA versus State Plans Download CSV
Standard groupFederal violationsFederal serious %Federal median initialFederal median currentState Plan violationsState Plan serious %State Plan median initialState Plan median current
Exit routes and emergency plans (1910.36 to 1910.39)4,10857.3$6,250$4,0005,60455.9$2,100$1,400
Portable fire extinguishers (1910.157)2,79737.2$4,610$2,6786,46139.4$850$700
Flammable liquids (1910.106)83681.0$6,620$4,1731,31280.3$1,518$1,052
Construction fire protection (1926.150 to 1926.152)50462.9$3,511$2,67869630.0$375$300
Other fire protection, Subpart L (1910.155 to 1910.165)14553.1$7,172$5,00095180.2$2,400$1,538
All coded fire standards8,39053.2$5,628$3,52615,02451.3$1,300$900

Medians cover items with a penalty above $0.

Source: [1][2] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal)

Which industries draw OSHA fire citations

Manufacturing leads in volume for three of the five standard groups. Public sector workplaces lead in extinguisher citations per inspection.

Top three NAICS sectors for each fire standard group Download CSV
Standard groupRankNAICS sector (2022)ViolationsShare of group %
Exit routes and emergency plans (1910.36 to 1910.39)1Manufacturing2,31723.9
Exit routes and emergency plans (1910.36 to 1910.39)2Retail Trade1,43314.8
Exit routes and emergency plans (1910.36 to 1910.39)3Public Administration1,16712.0
Portable fire extinguishers (1910.157)1Manufacturing2,11622.9
Portable fire extinguishers (1910.157)2Public Administration1,39015.0
Portable fire extinguishers (1910.157)3Retail Trade7768.4
Flammable liquids (1910.106)1Manufacturing95444.4
Flammable liquids (1910.106)2Construction24311.3
Flammable liquids (1910.106)3Other Services (except Public Administration)1808.4
Construction fire protection (1926.150 to 1926.152)1Construction1,15195.9
Construction fire protection (1926.150 to 1926.152)2Manufacturing141.2
Construction fire protection (1926.150 to 1926.152)3Administrative and Support and Waste Management and Remediation Services80.7
Other fire protection, Subpart L (1910.155 to 1910.165)1Public Administration76669.9
Other fire protection, Subpart L (1910.155 to 1910.165)2Manufacturing978.9
Other fire protection, Subpart L (1910.155 to 1910.165)3Retail Trade444.0

Sector of the inspected establishment, NAICS 2022 two-digit titles.

Source: [1][2][16] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Census Bureau

Extinguisher citations per 1,000 inspections, by industry sector

NAICS 2022 sectors with the most 1910.157 violations, FY2021 to FY2025

Extinguisher citations per 1,000 inspections, by industry sectorHorizontal bar chart. Public Administration has 123.56 extinguisher citations per 1,000 inspections, Utilities 93.95, Educational Services 73.31 and Construction 4.87.per 1,000 inspectionsPublic Administration124Utilities94.0Educational Services73.3Other Services (except Public Administrati64.8Accommodation and Food Services49.2Retail Trade48.5Wholesale Trade46.7Transportation and Warehousing40.7Administrative and Support and Waste Manag40.3Manufacturing35.4Health Care and Social Assistance22.6Construction4.87

Source: FLS analysis of DOL OSHA Violation and Inspection bulk files; Census NAICS 2022 titles

Manufacturing accounts for 2,116 extinguisher violations, 22.9% of the total, and 954 flammable liquid violations, 44.4%. Per inspection, Public Administration leads at 123.56 extinguisher violations per 1,000 inspections, followed by Utilities at 93.95. Construction, the most inspected sector, runs at 4.87 under 1910.157 because construction sites are cited under 1926.150 instead: 1,151 of the 1,200 construction fire protection violations came from construction establishments.

Transportation and Warehousing recorded 575 extinguisher violations, 40.67 per 1,000 inspections. Facility managers can compare these figures with our warehouse fire safety guide.

State-by-state extinguisher citation rates

Rates range from 219.15 per 1,000 inspections in Connecticut to 1.61 in South Dakota, driven largely by public sector programs and inspection mix.

Extinguisher citations per 1,000 OSHA inspections, by state

1910.157 violations per 1,000 inspections opened FY2021 to FY2025; WA, CA, OR and MI omitted because their State Plans cite state code numbers

Extinguisher citations per 1,000 OSHA inspections, by stateUS tile map of extinguisher citation rates. Connecticut is highest at 219.15 per 1,000 inspections, followed by New Mexico at 146.24 and Tennessee at 130.83; Texas is at 17.04 and Florida at 15.74.AK: 71.7AK71.7ME: 122ME122VT: 23.5VT23.5NH: 15.0NH15.0WAID: 8ID8MT: 4.74MT4.74ND: 3.38ND3.38MN: 7.88MN7.88IL: 29.9IL29.9WI: 10.6WI10.6MINY: 30.6NY30.6RI: 17.1RI17.1MA: 15.3MA15.3ORNV: 34.0NV34.0WY: 13.1WY13.1SD: 1.61SD1.61IA: 24.8IA24.8IN: 9.96IN9.96OH: 12.8OH12.8PA: 20.1PA20.1NJ: 52.2NJ52.2CT: 219CT219CAUT: 11.7UT11.7CO: 8.35CO8.35NE: 5.18NE5.18MO: 5.13MO5.13KY: 25.4KY25.4WV: 13.5WV13.5VA: 66.0VA66.0MD: 71.8MD71.8DE: 22.6DE22.6AZ: 113AZ113NM: 146NM146KS: 5.83KS5.83AR: 16.2AR16.2TN: 131TN131NC: 51.8NC51.8SC: 13.7SC13.7DC: 14.3DC14.3OK: 9.96OK9.96LA: 18.0LA18.0MS: 15.2MS15.2AL: 21.5AL21.5GA: 24.2GA24.2HI: 115HI115TX: 17.0TX17.0FL: 15.7FL15.7PR: 90.6PR90.61.61 to 8.358.35 to 13.713.7 to 17.117.1 to 25.425.4 to 71.871.8 to 219per 1,000 inspections

Source: FLS analysis of DOL OSHA Violation and Inspection bulk files (2026-10-27)

Extinguisher (1910.157) citations per 1,000 inspections, by state Download CSV
Show all 53 rows
StateInspections FY2021 to FY20251910.157 violations1910.157 per 1,000 inspectionsMajority jurisdiction
CT3,760824219.15Federal
VI575116201.74Federal
NM971142146.24State plan
TN7,521984130.83State plan
ME1,544188121.76Federal
HI2,580297115.12State plan
AZ2,735309112.98State plan
PR5,18647090.63State plan
MD6,32645471.77State plan
AK2,03614671.71State plan
VA10,02866266.02State plan
NJ10,67755752.17Federal
NC9,67250151.8State plan
NV5,58219034.04State plan
NY15,23246630.59Federal
IL13,50340429.92Federal
KY4,56411625.42State plan
IA3,0657624.8State plan
GA7,18317424.22Federal
VT8922123.54State plan
DE1,1082522.56Federal
AL4,0088621.46Federal
PA11,39922920.09Federal
LA2,1653918.01Federal
RI1,6392817.08Federal
TX19,90033917.04Federal
AR1,2332016.22Federal
FL11,75318515.74Federal
MA7,90212115.31Federal
MS1,5822415.17Federal
NH1,6712514.96Federal
DC7701114.29Federal
SC2,1212913.67State plan
WV1,4111913.47Federal
WY7611013.14State plan
OH10,95414012.78Federal
UT4,2054911.65State plan
WI7,2647710.6Federal
OK2,711279.96Federal
IN4,720479.96State plan
CO4,908418.35Federal
ID1,500128.0Federal
MN6,600527.88State plan
CA33,3862126.35State plan (state code numbering)
KS2,914175.83Federal
NE1,931105.18Federal
MO4,481235.13Federal
MT1,26564.74Federal
MI18,128844.63State plan (state code numbering)
OR13,274533.99State plan (state code numbering)
ND1,18443.38Federal
WA26,272793.01State plan (state code numbering)
SD1,24121.61Federal

States and territories with at least 500 inspections opened FY2021 to FY2025. Rates for WA, CA, OR and MI understate fire citations because their State Plans cite state code numbers.

Source: [1][2][13] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); OSHA (osha.gov page, archived copy by Internet Archive on 2026-10-17)

Connecticut (219.15 per 1,000) and New Mexico (146.24) lead. Connecticut's State Plan covers only state and local government workers, and 715 of Connecticut's 824 extinguisher violations came from State Plan inspections of local government workplaces. Large federal states sit lower: Texas at 17.04 and Florida at 15.74. Rates for Washington (3.01), California (6.35), Oregon (3.99) and Michigan (4.63) reflect only the federal share of their inspections plus the few State Plan items written under 29 CFR numbers.

Clear industrial corridor leading to an exit door with a panic bar and emergency light
Illustrative photograph. Generated image, not a specific project.

FY2021 to FY2025: extinguisher citations peaked in FY2024

Extinguisher violations rose 63.5% from FY2021 to FY2024 and fell 13.9% in FY2025 as federal inspections dropped.

Five-year trend in fire citations and extinguisher citation rates Download CSV
Fiscal year (inspection opened)InspectionsFire violations1910.157 violations1910.157 per 1,000 inspections, Federal1910.157 per 1,000, all State Plans1910.157 per 1,000, State Plans excl. WA, CA, OR, MIFire share of all violations %
FY202155,9393,7421,36016.2230.5957.653.45
FY202265,2184,6491,77316.9436.9673.823.72
FY202369,1775,1691,98719.9337.3377.733.78
FY202471,7365,2922,22320.540.7783.723.86
FY202568,7034,5621,91515.5237.673.823.41

Fiscal year of the inspection open date. FY2025 cases opened by 2025-09-30.

Source: [1][2] U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal); U.S. Department of Labor, Occupational Safety and Health Administration (DOL Open Data Portal)

Extinguisher violations grew from 1,360 in FY2021 to 2,223 in FY2024, then fell to 1,915 in FY2025. The federal rate moved from 16.22 per 1,000 inspections in FY2021 to 20.5 in FY2024 and 15.52 in FY2025, while federal inspections fell 12.6% between FY2024 and FY2025. Fire standards held between 3.41% and 3.86% of all violations each year from FY2022 to FY2025. Exit lighting and marking rules are explained in our emergency lighting inspection guide.

What this index measures and what it does not

This is a federal workplace safety dataset. It does not measure local fire code enforcement, fire incidents or workplace fire deaths.

OSHA citations record what a compliance officer found during a workplace inspection. A city fire inspection is a separate program under the adopted fire code, and an extinguisher defect can appear in both systems. Our city fire code violations report covers the local side. Workplace fire deaths are a separate topic and are not counted here.

The most recent comparable published count we found is from FY2011, when Safety+Health reported 1,430 federal 1910.157 violations from OSHA's older IMIS system (Safety+Health). That figure uses a different system and year and is context only.

Key findings

  1. 1910.157(c)(1), the duty to provide extinguishers and mount, locate and identify them so they are readily accessible, was cited 3,192 times in inspections opened FY2021 to FY2025, the most of any fire subparagraph (United States, Federal OSHA and State Plans).[1][5]
  2. Blocked or obstructed exit routes, 1910.37(a)(3), were cited 2,469 times over FY2021 to FY2025, and 61.2% of those items were classified serious.[1][6]
  3. The monthly visual inspection requirement, 1910.157(e)(2), drew 2,378 violations over FY2021 to FY2025; 30.0% were serious and the median initial penalty for items with a penalty was $700.[1][5]
  4. The annual maintenance requirement, 1910.157(e)(3), drew 1,849 violations over FY2021 to FY2025 with a median initial penalty of $2,500 for items with a penalty.[1][5]
  5. Monthly inspection and annual maintenance items together total 4,227 violations, 45.7% of all 1910.157 violations in FY2021 to FY2025.[1]
  6. Across all coded fire standards, initial penalties of $61,336,140 fell to $42,148,499 current penalties, a 31.3% reduction (inspections opened FY2021 to FY2025, nominal dollars).[1]
  7. Exit route and emergency planning items (1910.36 to 1910.39) account for $28,808,863 of current fire penalties, 68.4% of the total, over FY2021 to FY2025.[1]
  8. Only 38.7% of extinguisher violations were classified serious in FY2021 to FY2025, compared with 80.5% for flammable liquids (1910.106) and 56.4% for exit routes.[1]
  9. 71.7% of extinguisher items carried a $0 initial penalty, compared with 59.9% across all coded fire standards (FY2021 to FY2025).[1]
  10. Federal OSHA cited 1910.157 at 18.0 violations per 1,000 inspections over FY2021 to FY2025; State Plans that cite federal standard numbers did so at 73.48 per 1,000.[1][2][13]
  11. Among private employers only, the State Plan extinguisher rate was 44.16 per 1,000 inspections against 15.75 for Federal OSHA, 2.8 times higher (FY2021 to FY2025).[1][2]
  12. The median initial penalty for an extinguisher item with a penalty was $4,610 in federal inspections and $850 in State Plan inspections (FY2021 to FY2025).[1][2]
  13. Manufacturing accounts for 2,116 extinguisher violations (22.9%), 2,317 exit route violations (23.9%) and 954 flammable liquid violations (44.4%) over FY2021 to FY2025.[1][2][16]
  14. Extinguisher violations rose from 1,360 in FY2021 to 2,223 in FY2024, then fell to 1,915 in FY2025.[1][2]

Summary for decision makers

  • Fire protection standards produced 23,414 violations in 14,586 inspections opened from FY2021 to FY2025, out of 641,207 violations in 330,773 inspections.
  • Portable extinguishers (29 CFR 1910.157) and exit routes plus emergency plans (1910.36 to 1910.39) account for 81.0% of fire violations.
  • The monthly visual inspection rule, 1910.157(e)(2), ranks third with 2,378 violations; the annual maintenance rule, 1910.157(e)(3), ranks fourth with 1,849.
  • Initial fire penalties totaled $61,336,140; current penalties total $42,148,499, a 31.3% reduction after settlements and contests.
  • Exit route and emergency planning items carry 68.4% of current fire penalty dollars even though extinguisher items are nearly as numerous.
  • State Plans that cite federal standard numbers record 73.48 extinguisher violations per 1,000 inspections, 4.08 times the federal rate of 18.0.
  • Manufacturing is the leading sector for extinguisher, exit route and flammable liquid citations; Public Administration has the highest extinguisher rate at 123.56 per 1,000 inspections.

Questions people ask

What are the OSHA fire extinguisher monthly inspection requirements?

29 CFR 1910.157(e)(2) requires portable extinguishers to be visually inspected monthly. In inspections opened FY2021 to FY2025, Federal OSHA and State Plans cited this paragraph 2,378 times, 30.0% as serious.

Is there an OSHA fire extinguisher inspection checklist?

The federal rule does not set a checklist. 1910.157(e)(2) requires a monthly visual inspection, and 1910.157(e)(3) requires an annual maintenance check with the date recorded and kept for one year after the last entry or the life of the shell, whichever is less (eCFR, current 2026-10-23).

How much is an OSHA fine for fire extinguishers?

For extinguisher items with a penalty in FY2021 to FY2025, the median initial penalty was $4,610 in federal inspections and $850 in State Plan inspections. The federal maximum for a serious violation is $16,550 for penalties proposed after January 15, 2025.

Which industries get the most OSHA fire citations?

Manufacturing leads, with 2,116 extinguisher violations, 2,317 exit route violations and 954 flammable liquid violations in FY2021 to FY2025. Public Administration has the highest extinguisher rate at 123.56 per 1,000 inspections.

Do State Plans cite fire extinguishers more than federal OSHA?

Yes. State Plans that cite federal standard numbers recorded 73.48 extinguisher violations per 1,000 inspections over FY2021 to FY2025, against 18.0 for Federal OSHA. Among private employers the gap is 44.16 versus 15.75.

For journalists and researchers

If you cite only a few, cite these

  1. 1910.157(c)(1) was the most cited OSHA fire subparagraph in FY2021 to FY2025, with 3,192 violations.[1]
  2. Initial OSHA fire penalties of $61,336,140 fell 31.3% to $42,148,499 (inspections opened FY2021 to FY2025).[1]
  3. Federal OSHA cited portable extinguishers at 18.0 per 1,000 inspections over FY2021 to FY2025.[1][2]

Most quotable statistics

  • OSHA and State Plan inspectors cited fire protection standards 23,414 times in inspections opened from FY2021 to FY2025.[1][2]
  • The monthly fire extinguisher inspection rule, 29 CFR 1910.157(e)(2), was cited 2,378 times in FY2021 to FY2025, the third most cited fire subparagraph.[1]
  • Fire violations from FY2021 to FY2025 inspections drew $61.3 million in initial penalties; $42.1 million remains after reductions, a 31.3% cut.[1]
  • State Plans that cite federal standard numbers write extinguisher violations at 73.48 per 1,000 inspections, 4.08 times the federal rate of 18.0 (FY2021 to FY2025).[1][2]
  • 71.7% of OSHA extinguisher violation items in FY2021 to FY2025 carried a $0 initial penalty.[1]
  • Exit route and emergency plan items hold 68.4% of current OSHA fire penalty dollars from FY2021 to FY2025 inspections.[1]

Press summary

A Fire Life and Safety analysis of the Department of Labor's OSHA enforcement files finds 23,414 fire protection violations in 330,773 Federal OSHA and State Plan inspections opened from FY2021 to FY2025. The most cited fire subparagraph is 29 CFR 1910.157(c)(1), the duty to provide and mount accessible fire extinguishers, with 3,192 violations, followed by obstructed exit routes with 2,469. The osha fire extinguisher inspection requirements for monthly checks and annual maintenance drew 2,378 and 1,849 violations. Fire violations carried $61.3 million in initial penalties and $42.1 million after reductions, a 31.3% cut. Exit route items hold 68.4% of current penalty dollars. State Plans that cite federal standard numbers record extinguisher violations at 73.48 per 1,000 inspections, 4.08 times the federal rate. Manufacturing leads three of five standard groups by volume. The data, tables and code are published under CC BY 4.0.

Suggested headlines

  • OSHA cited fire extinguisher access 3,192 times in five years
  • Monthly extinguisher checks rank third among OSHA fire citations
  • OSHA fire penalties fall 31.3% from proposal to current amount
  • State Plans cite extinguishers four times as often as Federal OSHA
  • Exit route items carry 68.4% of OSHA fire penalty dollars

How to cite this report

Fire Life and Safety. (2026). OSHA Fire Safety Citations, FY2021 to FY2025: OSHA Fire Extinguisher Inspection Requirements and Exit Rules Ranked. Retrieved from https://firelifeandsafety.com/reports/osha-fire-safety-citations/

Reuse license

Data and tables are licensed CC BY 4.0. Attribution: “Source: Fire Life and Safety, OSHA Fire Safety Citations, FY2021 to FY2025: OSHA Fire Extinguisher Inspection Requirements and Exit Rules Ranked” with a link to this page.

Download the data

Every table in this report is available as a CSV under CC BY 4.0. The fact sheet lists each value with its source URL and access date.

Frequently asked questions

What is the most cited OSHA fire protection standard?

By subparagraph, 1910.157(c)(1) on providing and mounting portable extinguishers, with 3,192 violations in inspections opened FY2021 to FY2025. By section, exit routes in 1910.37 had 6,806 violations and 1910.157 had 9,258.

How often does OSHA cite the monthly extinguisher inspection rule?

1910.157(e)(2) was cited 2,378 times in FY2021 to FY2025, with a peak of 571 in FY2024.

How often does OSHA cite the annual extinguisher maintenance rule?

1910.157(e)(3) was cited 1,849 times in FY2021 to FY2025, with 433 in FY2024 and 411 in FY2025.

Is a missed monthly extinguisher inspection a serious violation?

Usually not. 30.0% of 1910.157(e)(2) items in FY2021 to FY2025 were classified serious; most were other-than-serious.

What is the maximum OSHA penalty in 2026?

The 2025 amounts still apply: $16,550 per serious or other-than-serious violation and $165,514 per willful or repeated violation, because the Department of Labor made no 2026 inflation adjustment (91 FR 31358, 2026-05-27).

Are OSHA penalties reduced after citation?

Often. Current fire penalties of $42,148,499 are 31.3% below the $61,336,140 initially proposed for inspections opened FY2021 to FY2025.

Are fire protection standards on OSHA's Top 10 list?

No fire standard is on the FY2025 federal Top 10. Over FY2021 to FY2025, 1910.37 ranks 21st and 1910.157 23rd among sections cited by Federal OSHA in our count.

Which exit route rules are cited most?

1910.37(a)(3), exit routes free and unobstructed, with 2,469 violations, then 1910.37(b)(2), exit signs, with 1,699, and 1910.36(d)(1), exit doors that open from the inside, with 772 (FY2021 to FY2025).

Do construction sites get cited under 1910.157?

Rarely. Construction sites are cited under 1926.150, whose paragraph (c)(1) on extinguishers and small hose lines drew 681 violations in FY2021 to FY2025; construction runs at 4.87 extinguisher citations per 1,000 inspections under 1910.157.

Does this report name cited employers?

No. The index is aggregate only. It reports 23,414 violations by standard, year, jurisdiction, sector and state, without establishment names.

Methodology

Data: the U.S. Department of Labor OSHA Violation and Inspection bulk files from the DOL Open Data Portal (data.dol.gov), both last modified 2026-10-27 and downloaded the same day without an API key. The older enforcedata.dol.gov catalog now redirects to data.dol.gov. OSHA's own query pages (osha.gov/ords/imis) returned a CAPTCHA to automated requests and were not used. The raw zip files are saved unmodified in raw/.

Selection: inspections opened from October 1, 2020 to September 30, 2025 (FY2021 to FY2025) with an inspection scope other than D (no inspection conducted), 330,773 in total. Violations marked deleted were dropped. A violation was coded as fire protection when its standard field begins with 1910.36, 1910.37, 1910.38, 1910.39, 1910.106, 1910.155 to 1910.165 or 1926.150 to 1926.152. Fiscal year follows the inspection open date, as on OSHA's own frequently cited standards pages.

Jurisdiction: an inspection is State Plan when the third digit of its reporting office code is 5. In states without a State Plan, nearly all inspections carried a code other than 5, and private sector inspections in public-only State Plan states such as Connecticut also carried other codes, which matches OSHA's State Plan list. Washington, California and most of Oregon and Michigan cite state rule numbers, so their fire citations are largely invisible to a 29 CFR filter; State Plan rates are therefore shown with and without them.

Measures: counts are cited items. Serious, other-than-serious, repeat and willful shares use the viol_type codes S, O, R and W. Penalty totals and medians use the initial_penalty and current_penalty fields in nominal dollars; medians exclude items at $0 because grouped violations carry one penalty. Sector uses the first two digits of the establishment NAICS code with Census 2022 sector titles. State uses the site state. Requirement summaries are paraphrased from eCFR text current as of 2026-10-23; no regulation text is reproduced at length.

Limitations: citations measure enforcement activity, not hazard prevalence; they depend on where inspectors go, and federal inspections are more construction-heavy (51.5%) than State Plan inspections (36.5%). Penalties for recent cases can still change through contest or settlement. The data dictionary does not spell out viol_type letters; we read them as the categories in 29 U.S.C. 666 and 29 CFR 1903.15. No employer is named. Conflicting figures: where OSHA's published Top 10 (single year, federal only) differs from our pooled ranks, both are shown with their scope.

This report is a reference summary of public enforcement data. It is not legal advice; requirements depend on the standard as adopted by your State Plan or local fire code. Last updated 2026-10-27. Scripts in scripts/ rebuild every table from the raw files.

This report presents published data with its limitations. It is not legal, engineering, financial or investment advice. Requirements depend on the code edition your state and local fire marshal have adopted; confirm with your authority having jurisdiction.

Sources, ranked by quality

Tier 1: primary and official sources (16)

Tier 3: journalism and expert commentary (1)

  • [17] Safety+Health magazine, National Safety Council. Beyond OSHA's Top 10. FY2011 IMIS data. Accessed 2026-10-27.

Never miss an inspection date. Get a printable calendar for your building.

Get your free inspection calendar